Testing of Corrosivity of Flammable Gases

  • IEC 60754-2
  • EN 50267
  • VDE 0482-267

This method determines whether insulating,- and coating materials for cables give off any corrosive fumes under flame treatment.

Test Setup:
Sample weight of 1g of not metallic element of a cable is heated in a furnace.  The pH value and conductivity of flammable gases is measured while dissolving in water.
Flame Temperature:
Minimum 935 °C
Test Time:
30 min

PH- value of the wash water must be at least 4.3 and the conductivity value of the wash water maximum 10 S/mm.

To top

Testing of Flammability Single Cores and Conductors

 
  • IEC 60332-1
  • (EN 50265-2)
  • neu: EN 60332-1
  • (VDE 0482-265-2-1)
  • neu: VDE 0482-332-1

This method tests flammability of any cable sample length of 60 cm.

Test Setup:
The cable  to be tested is fixed vertically and heated with a bunsen burner in 45° angle.
Flame Temperature:
Is adjusted according to the prescribed property of the bunsen burner.
Test Time:
Cabel Ø of </= 25 mm: 60 s
Cabel Ø of 25 < D < 50 mm: 120 s

Flame damages must end at least 50 mm under the top of the fixing clamp. Cables must be self-extinguishing.

To top

Testing of Flammability of Cable Bundles

  • IEC60332-3 cat.A/B/C/D
  • EN 50266-2-4
  • VDE 0482-266-...

This method checks a cable length of 3600 mm according to fire propagation.

Test Setup:
Dependent on variety of flame, cables are  fixed to a ladder, located close or with distance to each other. Cables can be fixed with several layers.
Flame Temperature:
Determined by prescribed amount of propane gas and air.
Test Time:
IEC Part 21/EN Teil 1: Category A F/R just for special application
IEC Part 22/EN Teil 2: Category A (7l brennbares material/m): 40 min
IEC Part 23/EN Teil 3: Category B (3,5 l flammable material/m): 40 min
IEC Part 24/EN Teil 4: Category C (1,5 l flammable material/m): 20 min
IEC Part 25/EN Teil 5: Category D (0,5 l flammable material/m): 20 min

Occurring damages of the cable must be visible maximum 2,5m from the bottom-end of the burner from top side.

To top

Testing of Flammability of Cable Bundles

  • IEC 61034
  • (EN 50268)
  • neu: EN 61034
  • (VDE 0482-268)
  • neu: VDE 0482-1034

This method checks the smoke emission of cables while burning or obstruction of view through burning cables.

Test Setup:
In a closed chamber a cable is burned by means of a flammable liquid. Transparency  of occurring fumes is measured optically.
Flame Temperature:
Determined by amount and composition of the liquid.
Test Time:
40 min

Transparency of the fume should be at least 60% at the end, if it is not specified differently.

To top

Testing of Circuit Integrity

  • IEC 60331 (FE)
  • BS 6387 /cat. C)
  • VDE 0472-Teil 814

Testing the circuit integrity determines both, the time period of a not charged cord under terms of flame and the minimum insulation properties.

Test Setup:
Cable is fixed horizontally, whereby core and shield is connected under voltage. Flamming is carried out  from bottom over a width of 1200mm.
Flame Temperature:
Minimum 750 °C
Test Time:
180 min

While flame treatment and additional cooling time of 12 hours, the power and the signal transmission must be given.  No short-circuit between conductors or coating as well as no open phase should occur. No pre-determined value in the standard is allowed to exceed attenuation increase.

To top

Testing of Circuit integrity ( Fire, Impact)

  • EN 50200
  • EN 50362
  • (BS 6387 /cat.Z)

Test Setup:
Cable (maximum diameter of 20mm) is installed onto a fixture and is exposed to flame from front. During the treatment the cable is hit every 5 min.in. angestoßen.
Flame Temperature:
842 °C
Test Time:
90 min.

This test is a must for every cable and conductor with a supply voltage up to 600/1000 V and for data communication cable without any supply voltage. No short-circuit between conductors and no open phase should occur. No pre-determined value in the standard is allowed to exceed attenuation increase.

To top

Testing of Circuit Integrity (Fire and Water)

  • BS 6387 (cat.W)

Test Setup:
Cable is fixed horizontally, whereby core and coat are connected electrically. Voltage is U/U. Flame treatment is carried over a width of 1500 mm. After 15 minutes  the sprinkle water dispenser is switched on.
Flame Temperature:
650 °C ± 40 °C
Test Time:
2 tests á 30 minutes

While fire treatment the signal and the power transmission must given in all cores. No short-circuit between conductors and coating.

To top

Testing of Functional Integrity of Electrical Cabling Systems according to DIN 4102 part 12 ( E30- E90)

Testing methods described above are not the same as the test of functional integrity of electrical cabling systems according to DIN 4102 part 12. Circuit Integrity “CI” checks just a single core or conductor but in that method a whole cable (practical orientated fixtures) is tested according to functional efficiency.

Test Setup:
Arrangement of a complete cable installation. That means cables including rings, fixtures, screws etc. are in a furnace.
Testing voltage for power lines 380V
Testing voltage for telecommunication cable 110V
Current load:3A
Test Time:
Testing time is subdivided in 2 functional integrity levels:
-E30 for a function integrity of at least 30 minutes
-E90 for a function integrity of at least 90 minutes

This method can be just carried out by official approved testing institutions.  After a successful test, a certificate is created, which is valid for installation directions. For optical fiber cables: No pre-determined value in the standard is allowed to exceed the attenuation.